Conventional Smoke Detector (SD3) OC05

Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version

  • Function
  • Specifications
  • Description
  • Additional information
  • Reviews (0)

Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version

Power supply specification
Main supply voltage:                                               13Vdc to 27 Vdc
Nominal main supply voltage:                              20 Vdc
Quiescent current (20 Vdc):                                  25µA
Alarm current (20 Vdc):                                         32ma
Power Down Reset Time:                                      >4s
Remote alarm indicator output:                            0V in standby / 3,3Vdc in alarm

Mechanical characteristics
Unit weight:                                                               130g
Unit dimensions (in mm):                                      H:55 D:104
IP index:                                                                     IP 32
Unit row material:                                                   ABS
Unit colour:                                                              White
Mounting mode:                                                      Base
Fixing - distance between centres:                      50mm to 60mm
under ceiling:                                                           2 screws Ø 4

Climatic characteristics
Operating temperature:                                       -10°C to +60°C
Storage temperature:                                            +10°C to +50°C
Operating relative humidity:                               ≤ 93%
Storage relative humidity:                                   ≤ 85%

Description

STANDARD EN54-7 Ed2000 / Full CE marking according to CPD
Number of certification: 0333 CPD 075 013
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OC05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
12V version of OC05 detectors is also available for security type systems

Additional information

Weight 23 kg
Dimensions 12 × 24 × 35 in
Color

Black, Green, Indigo

Size

Large, Medium, Small

Reviews

There are no reviews yet.


Be the first to review “Conventional Smoke Detector (SD3) OC05”