Conventional Smoke Detector (SD3) OC05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
12V version
Power supply specification
Main supply voltage: 13Vdc to 27 Vdc
Nominal main supply voltage: 20 Vdc
Quiescent current (20 Vdc): 25µA
Alarm current (20 Vdc): 32ma
Power Down Reset Time: >4s
Remote alarm indicator output: 0V in standby / 3,3Vdc in alarm
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55 D:104
IP index: IP 32
Unit row material: ABS
Unit colour: White
Mounting mode: Base
Fixing - distance between centres: 50mm to 60mm
under ceiling: 2 screws Ø 4
Climatic characteristics
Operating temperature: -10°C to +60°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
STANDARD EN54-7 Ed2000 / Full CE marking according to CPD
Number of certification: 0333 CPD 075 013
The Optical smoke detector analyzes an atmosphere by reflection of a light on the particles of smoke
according to TYNDALL effect. It detects especially the cold and visible smoke particles (0,3µm to 2µm)
produced in the early stages of a fire. The threshold of response of alarm is regulated to obtain the value
m=0,2db/m±0,03 according to standard EN54-7.
OC05 includes a developed technology (microprocessors, smd components) which means precision and
high reliability. A specific head detection fixed by a single ceiling base.
12V version of OC05 detectors is also available for security type systems
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Conventional Smoke Detector (SD3) OC05” Cancel reply
Related Products
-
0 out of 5
Conventional call point DMCL05
Main characteristics
CE certified according to CPD
Conform with the norm EN54-11
Key for reset
Separate key for test
No break glass
Red colour for Alarm status
Yellow colour for extinguishing command
Blue colour for Extinguishing abort -
0 out of 5
TD-2700TE-PR
Features
8 / 16 CH TVI / CVI / AHD video input
8 / 16 CH 5MP / 4MP / 4MP lite / 3MP / 1080P / 720P / WD1 recording
4 / 4 CH IPC 4MP / 3MP / 1080P / 960P / 720P recording
Adopt standard H.264 high profile compression format to get high-quality video at much lower bit rate
Intuitive and user-friendly Graphics User Interface ( GUI ), window style operation by mouse
Multi-mode recording: manual / timer / motion / sensor
Playback : 8 / 16 CH simultaneously playback
Search: time slice, time, event ( manual, sensor, motion ), tag search
Express and flexible backup via USB, network and so on
Pentaplex: preview, record, playback, backup and remote access
DHCP, DDNS, PPPoE network protocol, IE browse and CMS supported
Remote control via IE or CMS : preview, playback, backup, PTZ and configuration
Dual stream technology for local storage with high definition, remote network transmission and remote surveillance with mobile device
Multi-user online simultaneously
Authorization management, log review and device status review
HDMI 4K output, true high resolution display
Support PTZ preset and auto cruise, up to 255 presets and 8 cruises
Support NAT function and QRCode scanning by mobile phone and PAD
Powerful smart phone & Pad surveillance with iOS and Andriod OS
-
0 out of 5
ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management -
0 out of 5
Standard 2-8 Zone Conventional Fire Alarm Panel-C-tech
- Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) with optional EN54 part 13. compliance from the BSI.
- Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
- Manufactured by C-TEC in the UK.
- Two detector zone circuits.
- Four conventional sounder circuits*
- Integral 1.5A EN54-4/A2 compliant switch mode PSU.
- Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
- Two on-board relays (Fire and Fault).
- Two open-collector outputs (Remote and Reset).
- ‘Class change’ and alert inputs.
- Installer-friendly design.
- Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
- Low 25mA quiescent current.
- Multiple indicators.
- System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards and optional EN54-13 compliant sounder circuit boards.
- Space for two x 12V 3.3Ah VRLA batteries.
- Fully compatible with C-TEC’s ActiV range of conventional fire detectors.
-
0 out of 5
Addressable smoke detector (SD3) OA05
Main characteristics
Photoelectric scattering (Tyndall effect)
1 remote alarm indicator output
Lockable
Standard EN54-7
Cable section max 2,5mm²
8 levels sensitivity setting (0,1 dB/m to 0,35
dB/m)
Base isolator (option)
Base relay (option)
Constant sensitivity thanks to auto correction
Reviews