Honeywell Gent Conventional Control Panel: 13270-02LB

  • Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
  • Device options include a full range of smoke detectors (optical, beam and duct types),
    heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells
  • Sounder options include shallow base, deep base and bedhead sounder types
  • For installations where a high degree of weatherproofi ng is required, IP55 rated
    sounders, sirens and bells are available
  • Common accessories such as manual call
    points door release units and Xenon flashers can all be accommodated
  • False alarm verification feature to filter out false alarms is selectable through software

  • Function
  • Specifications
  • Description
  • Additional information
  • Reviews (0)
  • Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
  • Device options include a full range of smoke detectors (optical, beam and duct types),
    heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells
  • Sounder options include shallow base, deep base and bedhead sounder types
  • For installations where a high degree of weatherproofi ng is required, IP55 rated
    sounders, sirens and bells are available
  • Common accessories such as manual call
    points door release units and Xenon flashers can all be accommodated
  • False alarm verification feature to filter out false alarms is selectable through software
Model 2 Zone

13270-02LB

4 Zone

13270-04LB

8 Zone

13270-08LB

MAXIMUM LOAD PER ZONE 3mA
NO. OF SOUNDER CIRCUITS 2 4 8
MAX. SOUNDER CIRCUIT LOAD 500mA per circuit max 1A combined
BATTERIES 2 x 12V, 2.1 Ah min 2 x 12V, 2.1 Ah min 2 x 12V, 3.4 Ah
BATTERY STANDBY 72 hours (1mA per zone + 0.5A sounder load max)
WEIGHT (APPROX. WITH BATTERIES) 5.8Kg 5.8Kg 6.2 Kg
CABLE TYPE BS 6387, 2 core, min 1.5mm2 CSA
OPERATING ENVIRONMENT Indoor, 0 - 40ºC
CLASS CHANGE FACILITY Volt free contact - max distance 100m
APPROVALS BSI Approved (KM 553763)
CPD NO 0086-CPD-553764
RELEVANT STANDARD EN54: Parts 2 &4

Description

BSI approved to EN54: Parts 2 & 4, the Xenex control panel can be used on installations meeting BS 5839:Part1. Control panel options for 2-8 zones can be specifi ed.
Designed to simplify system installation, each Xenex panel contains an integral power supply and battery support to drive up to 8 alarm sounder circuits, 2 auxiliary relay contacts, a zone disablement facility and also one-man test and commissioning features.
Utilising LPCB approved conventional smoke or heat detectors, Xenex offers exceptional value for money.

Additional information

Weight 23 kg
Dimensions 12 × 24 × 35 in
Color

Black, Green, Indigo

Size

Large, Medium, Small

Reviews

There are no reviews yet.


Be the first to review “Honeywell Gent Conventional Control Panel: 13270-02LB”