Kentec UK Fire Suppression Releasing Panel Sigma-XT

Features

  • Approved to EN12094-1, EN54-2 and EN54-4
  • Three detection zones as standard
  • Any single zone or any combinations of zones can be configured to release
  • Configurable first stage sounder delays
  • Configurable detection delays
  • Zero time delay upon manual release option
  • Compatible with I.S. barriers
  • Non-latching zone input option to receive signals from                                                                             other systems such as aspirating equipment
  • Configurable extinguishant delays up to 60 seconds in 5 second steps
  • Configurable extinguishant duration up to 5 minutes in 5 second steps
  • Countdown timer shows time remaining until release
  • Supports up to seven, four wire status indicators
  • Built in Extract Fan control
Add to Wishlist
Add to Wishlist
Share

    Overview

    Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the Sigma XT extinguishant releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations.

    With three detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications.

    The extensive configuration options of the Sigma XT allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-1).

    The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety.

    The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status.

    With all of the electronics mounted on a single, easily removable, steel plate Sigma XT panels are both robust and easy to install.

    Sigma XT is supplied in an enclosure that matches the design and colour of the Sigma CP range.

    Weight 23 kg
    Dimensions 12 × 24 × 35 cm
    Size

    Large, Medium, Small

    Function

    Features

    • Approved to EN12094-1, EN54-2 and EN54-4
    • Three detection zones as standard
    • Any single zone or any combinations of zones can be configured to release
    • Configurable first stage sounder delays
    • Configurable detection delays
    • Zero time delay upon manual release option
    • Compatible with I.S. barriers
    • Non-latching zone input option to receive signals from                                                                             other systems such as aspirating equipment
    • Configurable extinguishant delays up to 60 seconds in 5 second steps
    • Configurable extinguishant duration up to 5 minutes in 5 second steps
    • Countdown timer shows time remaining until release
    • Supports up to seven, four wire status indicators
    • Built in Extract Fan control

    Specifications

    TECHNICAL SPEC:
    Construction 1.2mm mild sheet steel
    IP Rating IP30
    Finish Epoxy powder coated
    Colour – lid & box BS 00 A 05 grey – fine texture
    Colour – controls plate & labels RAL 7047 light grey – satin
    Weight 6kg
    Mains supply 230V AC +10%/-15% (100 Watts maximum)
    Mains supply fuse 1.6 Amp (F1.6A L250V)
    Power supply rating 3 Amps total including battery charge 28V +/- 2V
    Maximum ripple current 200 millivolts
    Battery type (Yuasa NP) Two 12 Volt 7Ah sealed lead acid in series
    Battery charge voltage 27.6VDC nominal (temperature compensated)
    Battery charge current 0.7A maximum
    Battery fuse 20mm, 3.15A glass
    Maximum current draw from batteries 3 Amps
    Quiescent current of panel in mains fail 0.095A
    R0V output Fused at 500mA with electronic fuse
    Sounder outputs 24V Fused at 500mA with electronic fuse
    Fault relay contact rating 30VDC 1A Amp maximum
    Fire relay contact rating 30VDC 1A Amp maximum
    Local fire relay contact rating 30VDC 1A Amp maximum
    First stage contact rating 30VDC 1A Amp maximum
    Second stage contact rating 30VDC 1A Amp maximum
    Extract contact rating 30VDC 1A Amp maximum
    Zone quiescent current 2mA maximum
    Terminal capacity 0.5mm² to 2.5mm² solid or stranded wire
    Number of detectors per zone Dependent on type (maximum 32)
    Number of sounders per circuit Dependent on type (max. 0.5A per sounder circuit)
    Detection circuit end of line 6K8 5% ½ Watt resistor
    Sounder circuit end of line 10K 5% ¼ Watt resistor
    Extinguishant output EOL 1N4004 Diode
    No. of detection circuits 3
    No. of sounder circuits 2 x 1st Stage, 1 x 2nd Stage
    Extinguishant release output Fused at 1 Amp
    Extinguishant release delay Adjustable 0 to 60 seconds (in 5 second steps)
    Extinguishant release duration Adjustable 60 to 300 seconds (in 5 second steps)
    SIL, AL, FLT, RST inputs Switched -ve, max resistance 100 Ohms
    Zone normal threshold 8K ohms to 1K ohm
    Detector alarm threshold 999 ohms to 400 ohms
    Call point alarm threshold 399 ohms to 100 ohms
    Short circuit threshold 99 ohms to 0 ohms
    Head removal condition 15.5 to 17.5 volts
    Monitored inputs normal threshold FP200 or equivalent
    Monitored inputs alarm threshold 8K ohms to 1K ohm
    Monitored inputs Short circuit threshold 999 ohms to 100 ohms
    Status unit/Ancillary board connection 99 ohms to 0 ohms
    Status unit power output Two wire RS485 connection
    Cabling Fused at 500mA with electronic fuse