HomeProductsFire Alarm SystemHEPHAIS 1600 Addressable Panel

HEPHAIS 1600 Addressable Panel

Main characteristics
400 addressable devices
1000 zones, 256 groups of command
Base: 2 loops (200 addr./ loop) or 4 open circuits (32
det./line)
2 programmable inputs / 2 programmable outputs on the
CPU board
2 programmable inputs on the front board
Jbus protocol for remote monitoring software
Detectors management (day/night, scheduled sensitivity,
pre-alarm, alarm confirmation)
Addressable sounders management
Manual/automatic management of monitored sounders line
Download software
Actuators function (activation/deactivation command
groups)

Add to Wishlist
Add to Wishlist
Share

    HEPHAIS 1600 NE is a control and indicating equipment (CIE) with zone and point address localization
    using microprocessor-based technology. It is designed to meet the requirements of standards EN54-2
    and EN54-4.
    HEPHAIS 1600 NE is an interactive-addressable panel and it can manage up to 400 devices on 2
    loops of detection or 128 addresses on 4 lines.
    The panel is made of a basis CPU board and control front panel. Optional remote front panel, relay
    module boards and sounder line splitter are also available.
    With its new functionalities, HEPHAIS 1600 NE provides a flexible solution for all Fire Detection
    Systems (FDS.
    HEPHAIS 1600 NE is reliable and easy to use equipment. Associated to interactive 05 detectors range,
    It is adapted to all types of required topologies and can manage up to 400 detectors or manual call
    points, that can be equipped of short-circuit isolator.
    Adapted to a large scale of application, HEPHAIS 1600 NE can answer to requirements of buildings like
    hotels, retiring houses, schools, but also small industries and manufactures, storage houses, office
    buildings, back office centres, thanks to its various and numerous outputs allowing many signalling and
    command orders.
    Field configuration, scheduled sensitivity and the manual setting constitute very useful start up modes
    which make HEPHAIS 1600 NE installation a quick and sure operation.
    The software TELEHEPHAIS1600 (download data) allows to configure advanced functionalities and
    exploit all the capacities of the panel up to 1000 zones and 256 command groups

    Weight 23 kg
    Dimensions 12 × 24 × 35 cm
    Size

    Large, Medium, Small

    Function

    Main characteristics
    400 addressable devices
    1000 zones, 256 groups of command
    Base: 2 loops (200 addr./ loop) or 4 open circuits (32
    det./line)
    2 programmable inputs / 2 programmable outputs on the
    CPU board
    2 programmable inputs on the front board
    Jbus protocol for remote monitoring software
    Detectors management (day/night, scheduled sensitivity,
    pre-alarm, alarm confirmation)
    Addressable sounders management
    Manual/automatic management of monitored sounders line
    Download software
    Actuators function (activation/deactivation command
    groups)

    Specifications

    Electrical specification
    Mains supply voltage:                    230Vac (-15%,+10%), 50Hz or 60Hz
    Operating voltage:                          26.4V to 29 Vdc
    Wiring:                                              2 x (0,6 to 1,5) mm² max, shielded / Length = 1500m max
    Batteries:                                          2 x 12V/7Ah
    Autonomy without mains:            1 hours in alarm (command)
    Autonomy for data storage out of voltage:     > 7 days
    Data storage:                                    Non volatile memory (Eeprom)
    Maximum current supplied:         5 A
    Mechanical characteristics
    Dimensions (mm) / weight (without batteries) 320 x 610 x 175 (h x w d) / 5Kg (without batteries)
    Material/colour ABS 5V/RAL 7035
    Climatic characteristics
    Operating temperature / Storage temperature -10°C to 50°C
    Operating relative humidity / Storage relative humidity  93% R.H./  80% R.H.
    Inputs/outputs
    Base: Max number of points / Max number of zones 400 points/1000 zones
    Base: Fire detection lines 2 loops or 4 open lines
    Fire alarm management Alarm, pre alarm, alarm confirmation, hours management
    day/night mode
    Memory events Up to 2700 events with date and hours
    Programmable outputs (fire alarm, fault, test zone, disabled
    point…) 3 x free contact relay outputs 50V/0,3A
    Programmable inputs (power. supply fault, reset, sounders
    activation…)
    2 x monitored inputs for external event management (fault,
    reset…)
    2 x monitored inputs on front panel
    Serial communication ports
    RS232 communication port programming with PC
    RS422 communication port for Jbus protocol for graphic
    monitoring
    On front panel
    RS232 for external printer
    2 x RS485 communication port for remote front panel
    (redundant communication)
    Sounders line 2 x monitored outputs 30V/1A (for the 2 lines)
    External power supply output 1 x 24V/0,5A
    Internal options
    C20R, 20 way programmable relays board NO/NC contacts potential free or resistive 50V/0,3A
    R7P2, 7 way programmable relays board NO/NC contacts potential free or resistive 50V/0,3A
    R12P2, 12 way programmable relays board NO/NC contacts potential free or resistive 50V/0,3A
    External options
    ALPHA RE remote control and indicating panel Serial connection (from 1 to 20 panels)