HomeProductsFire Alarm SystemHoneywell Gent Conventional He...
Honeywell Gent Conventional Heat Detector : Eco 1005
• Low current draw, Low profile design
• 580C operating temperature
• Operates at 12 and 24VDC
• Remote alarm test feature
• Easy Maintenance
• Range of detector bases available
• Remote LED Option
• Approved to EN54 –5:2000 Class A1R
• Approved to MED 96/98/EC (Amendment 2009/26/EC)
• Extended warranty
The ECO1005 A thermal detector belongs to System Sensor’s ECO1000 range of detectors. ECO1000 is a range of conventional detectors, which have been produced using the latest in manufacturing technology and supplied with an array of advanced features, making them ‘better by design’. The ECO1005 A thermal detector uses a state of the art thermal element combined with an application specific integrated circuit (ASIC)to provide quick and accurate
detection of fires. The detector incorporates both rate of rise and static elements and is suitable for all areas where the ambient conditions do not normally exhibit rapid changes in temperature.
A laser-based hand held Remote Test Unit can be used in conjunction with the range of ECO1000 detectors for alarm test purposes. The unit transmits a coded message, preventing spurious alarms being generated by other laser-based devices. With a range of several metres, the hand held test unit provides an effortless way of remotely alarm testing the range of ECO1000 detectors and removes the need for any direct physical access to the detector by the user.
| Weight | 23 kg |
|---|---|
| Dimensions | 12 × 24 × 35 cm |
| Size | Large, Medium, Small |
- Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
- Device options include a full range of smoke detectors (optical, beam and duct types),
heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells - Sounder options include shallow base, deep base and bedhead sounder types
- For installations where a high degree of weatherproofi ng is required, IP55 rated
sounders, sirens and bells are available - Common accessories such as manual call
points door release units and Xenon flashers can all be accommodated - False alarm verification feature to filter out false alarms is selectable through software
Function
Specifications
| Model | 2 Zone
13270-02LB |
4 Zone
13270-04LB |
8 Zone
13270-08LB |
| MAXIMUM LOAD PER ZONE | 3mA | ||
| NO. OF SOUNDER CIRCUITS | 2 | 4 | 8 |
| MAX. SOUNDER CIRCUIT LOAD | 500mA per circuit max 1A combined | ||
| BATTERIES | 2 x 12V, 2.1 Ah min | 2 x 12V, 2.1 Ah min | 2 x 12V, 3.4 Ah |
| BATTERY STANDBY | 72 hours (1mA per zone + 0.5A sounder load max) | ||
| WEIGHT (APPROX. WITH BATTERIES) | 5.8Kg | 5.8Kg | 6.2 Kg |
| CABLE TYPE | BS 6387, 2 core, min 1.5mm2 CSA | ||
| OPERATING ENVIRONMENT | Indoor, 0 – 40ºC | ||
| CLASS CHANGE FACILITY | Volt free contact – max distance 100m | ||
| APPROVALS | BSI Approved (KM 553763) | ||
| CPD NO | 0086-CPD-553764 | ||
| RELEVANT STANDARD | EN54: Parts 2 &4 | ||
Only logged in customers who have purchased this product may leave a review.






Reviews
There are no reviews yet.