HomeProductsFire Alarm SystemHoneywell Gent Conventional Co...
Honeywell Gent Conventional Control Panel: 13270-02LB
- Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
- Device options include a full range of smoke detectors (optical, beam and duct types),
heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells - Sounder options include shallow base, deep base and bedhead sounder types
- For installations where a high degree of weatherproofi ng is required, IP55 rated
sounders, sirens and bells are available - Common accessories such as manual call
points door release units and Xenon flashers can all be accommodated - False alarm verification feature to filter out false alarms is selectable through software
Add to Wishlist
Add to Wishlist
Share
CategoryFire Alarm System
BSI approved to EN54: Parts 2 & 4, the Xenex control panel can be used on installations meeting BS 5839:Part1. Control panel options for 2-8 zones can be specifi ed.
Designed to simplify system installation, each Xenex panel contains an integral power supply and battery support to drive up to 8 alarm sounder circuits, 2 auxiliary relay contacts, a zone disablement facility and also one-man test and commissioning features.
Utilising LPCB approved conventional smoke or heat detectors, Xenex offers exceptional value for money.
| Weight | 23 kg |
|---|---|
| Dimensions | 12 × 24 × 35 cm |
| Size | Large, Medium, Small |
- Xenex deploys devices on conventional radial wiring layouts using standard 2-core cable
- Device options include a full range of smoke detectors (optical, beam and duct types),
heat detectors (fi xed temperature or rate of rise types), sounders, strobes and bells - Sounder options include shallow base, deep base and bedhead sounder types
- For installations where a high degree of weatherproofi ng is required, IP55 rated
sounders, sirens and bells are available - Common accessories such as manual call
points door release units and Xenon flashers can all be accommodated - False alarm verification feature to filter out false alarms is selectable through software
Function
Specifications
| Model | 2 Zone
13270-02LB |
4 Zone
13270-04LB |
8 Zone
13270-08LB |
| MAXIMUM LOAD PER ZONE | 3mA | ||
| NO. OF SOUNDER CIRCUITS | 2 | 4 | 8 |
| MAX. SOUNDER CIRCUIT LOAD | 500mA per circuit max 1A combined | ||
| BATTERIES | 2 x 12V, 2.1 Ah min | 2 x 12V, 2.1 Ah min | 2 x 12V, 3.4 Ah |
| BATTERY STANDBY | 72 hours (1mA per zone + 0.5A sounder load max) | ||
| WEIGHT (APPROX. WITH BATTERIES) | 5.8Kg | 5.8Kg | 6.2 Kg |
| CABLE TYPE | BS 6387, 2 core, min 1.5mm2 CSA | ||
| OPERATING ENVIRONMENT | Indoor, 0 – 40ºC | ||
| CLASS CHANGE FACILITY | Volt free contact – max distance 100m | ||
| APPROVALS | BSI Approved (KM 553763) | ||
| CPD NO | 0086-CPD-553764 | ||
| RELEVANT STANDARD | EN54: Parts 2 &4 | ||
Only logged in customers who have purchased this product may leave a review.






Reviews
There are no reviews yet.